Manual 2100-571 Page 1 of 31MV4000 SERIES SOLID STATE DUAL UNIT LEAD/LAG CONTROLLERfor use with H-SeriesWall Mount Air Conditioners INSTALLATION INST
Manual 2100-571Page 10 of 31HUMIDITY CONTROL OPTIONNote: This function is not available if controller is congured for heat pump.The standard air con
Manual 2100-571Page 11 of 313. 1-Stage Compressor Units with Newer ECONWMT Economizers (See Note A)1st stage cooling set point is the setting (
Manual 2100-571Page 12 of 312. 1-Stage Compressor Units with Newer ECONWMT Economizers (See Note A)1st stage cooling set point is the setting (
Manual 2100-571Page 13 of 31SPECIFICATIONS FOR OPTIONAL REMOTE COMMUNICATION BOARDCB4000 COMMUNICATION BOARDNote: If this communication board was not
Manual 2100-571Page 14 of 31USER PAGE 1. The designated Admin person can assign up to 9 additional users and set-up as Admin, Write or R
Manual 2100-571Page 15 of 31CONTROLLER WIRINGThe MV4000 can be used for controlling two (2) air conditioners with or without economizers. It can als
Manual 2100-571Page 16 of 31CU, AND SILVER MUST NOTE: ALL SENSORS AREPOLARITY SENSITIVE. COPPER LEAD MUST CONNECT TO LEAD TO AG2EF23EF32 COMP RUN ALA
Manual 2100-571Page 17 of 31CU, AND SILVER MUST NOTE: ALL SENSORS AREPOLARITY SENSITIVE. COPPER LEAD MUST CONNECT TO LEAD TO AG2 COMP RUN ALARMTERMIN
Manual 2100-571Page 18 of 31FIGURE 3MV4000-BC CONTROLLER CONNECTIONS1-STAGE (H**A/H**L SERIES) AIR CONDITIONERS – NO ECONOMIZERWITH ALARM BOARD &
Manual 2100-571Page 19 of 31FIGURE 4MV4000-BC CONTROLLER CONNECTIONS2-STAGE (HA*S/HL*S SERIES) AIR CONDITIONERS – NO ECONOMIZERSWITH ALARM BOARD &
Manual 2100-571 Page 2 of 31CONTENTSEcon. Failure & 2-Compressor Run Alarm ... 24Alarm Wiring ...
Manual 2100-571Page 20 of 31FIGURE 5MV4000-B CONTROLLER CONNECTIONS1-STAGE (H**A/H**L SERIES) AIR CONDITIONERSWITH (ECONWMT) ECONOMIZERSCU, AND SILVE
Manual 2100-571Page 21 of 31This page intentionally left blank.
Manual 2100-571Page 22 of 31FIGURE 7MV4000-BC CONTROLLER CONNECTIONS1-STAGE (H**A/H**L SERIES) AIR CONDITIONERSWITH (ECONWMT) ECONOMIZERSAND WITH ALA
Manual 2100-571Page 23 of 31This page intentionally left blank.
Manual 2100-571Page 24 of 31ALARM WIRINGAlarm relays can be wired for NO (close on alarm) or NC (open on alarm) strategy.Alarm relays can be used ind
Manual 2100-571Page 25 of 312ND STAGE COOLING ALARMThis alarm output is available for use if desired. It is important to note that in some installat
Manual 2100-571Page 26 of 31FIGURE 9ALARM BOARD CONNECTIONSFOR NORMALLY CLOSED "NC" OPEN-ON-ALARM STRATEGYIMPORTANT! LED display board is
Manual 2100-571Page 27 of 31FIGURE 10ALARM BOARD CONNECTIONSFOR NORMALLY OPEN "NO" CLOSE-ON-ALARM STRATEGYIMPORTANT! LED display board is
Manual 2100-571Page 28 of 31PROGRAMMING INSTRUCTIONSTo swap lead and lag unit positions, press the ADVANCE button.To enter the Program mode, press th
Manual 2100-571Page 29 of 31Material: 10 mil HP92WP lexanAdhesive: 7952MPPremask: 4075Colors: black, spot white, trans red, spot froste
Manual 2100-571Page 3 of 31Getting Other Information and PublicationsThese publications can help you install the air conditioner or heat pump. You c
Manual 2100-571Page 30 of 31FIGURE 11PARTS LIST DESCRIPTION DIAGRAMSEXP-63895132717123415 1141116101868
Manual 2100-571Page 31 of 31 Parts List Dwg.No.Part No. Description MV4000-B MV4000-BC AB3000-B CB40001 127-423-4 Control Box X X2 8612-038 Controll
Manual 2100-571Page 4 of 31SHIPPING DAMAGEUpon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage i
Manual 2100-571Page 5 of 31SPECIFICATIONS/FEATURES FOR MV4000-B CONTROLLERMV4000 Basic Controller•Input power: 18-32 VAC, 60/50Hz, power is supplied
Manual 2100-571Page 6 of 31LOCATED IN THE MV4000 PANEL BOXUnit #1 Terminal Block R – 24VAC hot from Unit C – 24VAC common from Unit Y – Compressor
Manual 2100-571Page 7 of 31LOW VOLTAGE FIELD WIRINGThe MV4000 is powered from the air conditioners that it is controlling, 24 VAC (18-32V) low voltag
Manual 2100-571Page 8 of 31FIRE SUPPRESSION CIRCUIT To disable the MV4000 and shut down both air conditioners, terminals F1 and F2 may be used. The
Manual 2100-571Page 9 of 31GENERAL PROGRAMMING OVERVIEWMV4000 CONTROLLER BUTTONS AND FUNCTIONOn/Off Button 1. Press and release the On/Off button t