Manual 2100-467K Page 1 of 24SINGLE PACKAGEAIR CONDITIONERSMODELS PA13242-A PA13302-A PA13362-A PA13362-B PA13422-A PA13422-B PA13422-C PA13482-
Manual 2100-467K Page 10 of 24INSTALLATIONLOCATIONGENERAL The unit must be located outside, or in a well ventilated area. It must not be in the spac
Manual 2100-467K Page 11 of 2436" min.24" min.24" min.The distance between1 inch clearanceAccessAir InletComp-Nearest StructureAir Inl
Manual 2100-467K Page 12 of 24FIGURE 4ELEVATED MOUNTING PLATFORMBoth legs must reston surface of platform32°F or lower climate12" min. if in48
Manual 2100-467K Page 13 of 24FIGURE 5CONDENSATE DRAIN TRAP5. OTHER INSTALLATIONS – Many other installations are possible with the packaged air co
Manual 2100-467K Page 14 of 24TABLE 6THERMOSTAT WIRE SIZETRANSFORMER TAPS230/208V, 1 phase and 3 phase equipment employ dual primary voltage transfo
Manual 2100-467K Page 15 of 24EY1120-445TH5220D1151Low Voltage WiringL2CO1Unit Control PanelBlockYCG RW1 W2EFY1CG RW1OY2 W2DAELAUXRGEBRC3LBThermostat
Manual 2100-467K Page 16 of 24START UPThese units require R-410A refrigerant and Polyol Ester oil.GENERAL:1. Use separate service equipment to avoid
Manual 2100-467K Page 17 of 24THREE PHASE SCROLL COMPRESSOR START UP INFORMATION(Models PA13362-B; PA13422-B, -C; PA13482-B, -C; PA13602-B, -C)All un
Manual 2100-467K Page 18 of 24LOW PRESSURE SWITCH, BYPASS, AND LOCKOUT SEQUENCE (Standard Feature)If the low pressure switch opens for more that 120
Manual 2100-467K Page 19 of 24FAN BLADE SETTINGSShown in Figure 8 are the correct fan blade setting dimensions for proper air delivery across the out
Manual 2100-467K Page 2 of 24CONTENTSGetting Other Informations and Publications ...3General InstructionsImportant ...
Manual 2100-467K Page 20 of 24(Continued on Page 20 in Table 11)TABLE 9PRESSURE TABLECOOLINGAir Temperature Entering Outdoor Coil Degree FLOW SIDE P
Manual 2100-467K Page 21 of 24TABLE 10PRESSURE TABLELOW SIDE PRESSURE +4 PSIGHIGH SIDE PRESSURE +10 PSIGTablesbaseduponratedCFM(airow)across
Manual 2100-467K Page 22 of 24SUCTION AND DISCHARGE TUBE BRAZINGCompliant Scroll compressors have copper plated steel suction and discharge tubes. T
Manual 2100-467K Page 23 of 24FIGURE 10NOTE: Bard Models PA13242; PA13302; PA13362-A, -B; PA13422-A, -B, -C; PA13482-A, -B, -C; PA13602-A, -B, -C c
Manual 2100-467K Page 24 of 24FIGURE 11TROUBLESHOOTING GE X13-SERIES ECM2.3™ MOTORS CONT’D.Model X13 Communication Diagnostics The X13 motor is c
Manual 2100-467K Page 3 of 24Getting Other Information and PublicationsThese publications can help you install the air conditioner or heat pump. You
Manual 2100-467K Page 4 of 24GENERAL INSTRUCTIONSIMPORTANTThe equipment covered in this manual is to be installed by trained, experienced service and
Manual 2100-467K Page 5 of 24TABLE 2ELECTRICAL SPECIFICATIONSModel PA13242-A PA13302-A PA13362-A PA13362-B PA13422-A PA13422-B PA13422-C PA13482-A P
Manual 2100-467K Page 6 of 24TABLE 3OPTIONAL FIELD INSTALLED HEATER PACKAGES ONLY TO BE USED WITH THE MODELS INDICATEDHeater PackageModelVolts &
Manual 2100-467K Page 7 of 24TABLE 4OPTIONAL FIELD INSTALLED ELECTRIC HEATER TABLEIMPORTANT: While this electrical data is presented as a guide, it
Manual 2100-467K Page 8 of 24FIGURE 1ADIMENSIONS OF UNITSReturn openingDrain accessSupply openingHigh voltage knockoutLow voltage knockoutaccess doo
Manual 2100-467K Page 9 of 24FIGURE 1BDIMENSIONS OF UNITSA BCDFEDAHGUNIT A B C D E F GHPA/PH1324, 1330,1336 7 3/16" 38 13/16" 36 3/4"