Manual 2100-401A
Page 1 of 21
INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE AIR CONDITIONERS
MODELS
WA4842
WA4843
WA6022
WA6023
Manual : 2100-401A
Supersedes: 2100-401
File: Volume III Tab 16
Date: 07-25-06
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Vista de pagina 0
1 2 3 4 5 6 ... 20 21

Indice de contenidos

Pagina 1 - Bryan, Ohio 43506

Manual 2100-401APage 1 of 21INSTALLATION INSTRUCTIONSWALL MOUNTEDPACKAGE AIR CONDITIONERSMODELSWA4842WA4843WA6022WA6023Manual : 2100-401ASupersedes: 2

Pagina 2 - CONTENTS

Manual 2100-401APage 10 of 21FIGURE 3MOUNTING INSTRUCTIONSWA6023, WA4843 ONLY

Pagina 3 - Page 3 of 21

Manual 2100-401APage 11 of 21FIGURE 4MOUNTING INSTRUCTIONSWA6022, WA4842 ONLY

Pagina 4 - ELECTRIC HEAT TABLE

Manual 2100-401APage 12 of 21FIGURE 5ELECTRIC HEAT CLEARANCE WARNINGA minimum of 1/4 inch clearance must be maintained betweenthe supply air

Pagina 5 - UNIT DIMENSIONS

Manual 2100-401APage 13 of 21FIGURE 6WALL MOUNTING INSTRUCTIONSFIGURE 7WALL MOUNTING INSTRUCTIONSSEE FIGURE 3 – MOUNTING INSTRUCTIONSSEE UNIT DIMEN

Pagina 6 - FIGURE 2

Manual 2100-401APage 14 of 21FIGURE 8COMMON WALL MOUNTING INSTALLATIONS

Pagina 7 - ELECTRICAL SPECIFICATIONS

Manual 2100-401APage 15 of 21WIRING – MAIN POWERRefer to the unit rating plate for wire sizing informationand maximum fuse or “HACR” type circuit br

Pagina 8 - CONDENSATE DRAIN

Manual 2100-401APage 16 of 21FIGURE 9UNIT 24V TERMINAL BOARD

Pagina 9 - WARNING

Manual 2100-401APage 17 of 21START UPIMPORTANT INSTALLER NOTEFor improved start up performance wash the indoor coilwith a dish washing detergent.CRANK

Pagina 10 - WA6023, WA4843 ONLY

Manual 2100-401APage 18 of 21Alarm Relay OutputAlarm terminal is output connection for applicationswhere alarm relay is employed. This terminal ispow

Pagina 11 - WA6022, WA4842 ONLY

Manual 2100-401APage 19 of 21The suction line temperatures in table above are basedupon 80° F dry bulb / 67° F wet bulb (50% R.H.)temperature and rate

Pagina 12 - WARNING

Manual 2100-401APage 2 of 21CONTENTSFiguresFigure 1 Unit Dimensions ... 5WA6023, WA4843Figure 2 Unit Dimensions ...

Pagina 13 - FOR ACTUAL DIMENSIONS

Manual 2100-401APage 20 of 21TABLE 9MAXIMUM ESP OF OPERATIONELECTRIC HEAT ONLYValues shown are for units equipped with standard1" throwaway filt

Pagina 14 - FIGURE 8

Manual 2100-401APage 21 of 21TABLE 11OPTIONAL ACCESSORIESWA6023A. WA6022AWA6023B, WA6022BWA4843A, WA4842AWA4843B, WA4842BtraPrebmuNnoitpircseD51-CMCt

Pagina 15 - WIRING – LOW VOLTAGE WIRING

Manual 2100-401APage 3 of 21Getting Other Information and PublicationsThese publications can help you install the airconditioner or heat pump. You ca

Pagina 16 - UNIT 24V TERMINAL BOARD

Manual 2100-401APage 4 of 21WALL MOUNT GENERAL INFORMATIONAIR CONDITIONING WALL MOUNT MODEL NOMENCLATUREWA 60 2 3 A 10

Pagina 17 - START UP

Manual 2100-401APage 5 of 21FIGURE 1UNIT DIMENSIONSWA6023, WA4843 ONLY

Pagina 18 - ADJUSTMENTS

Manual 2100-401APage 6 of 21FIGURE 2UNIT DIMENSIONSWA6022, WA4842 ONLY

Pagina 19 - TROUBLESHOOTING

Manual 2100-401APage 7 of 21TABLE 2ELECTRICAL SPECIFICATIONS1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of fiel

Pagina 20

Manual 2100-401APage 8 of 21SHIPPING DAMAGEUpon receipt of equipment, the carton should bechecked for external signs of shipping damage. Ifdamage is

Pagina 21 - OPTIONAL ACCESSORIES

Manual 2100-401APage 9 of 21INSTALLATION INSTRUCTIONSWALL MOUNTING INFORMATION1. Two holes for the supply and return air openingsmust be cut through